Applied Research – SCADA for Power Systems
13-week Applied Research course project
01 · Problem A case study for Engineering Technology students
Building on EPIC's experience delivering substation SCADA systems, I co-developed a training case study for Engineering Technology students.
02 · Approach Assignments that build one project
- I designed the students' Inductive University study plan.
- I wrote a series of reinforcement assignments: dynamic alarming, navigation and popups, event logging.
- Each assignment builds one part of the final project and includes optional extension challenges with a suggested approach.
- I built the reference project: a reference solution followed each assignment, so students could check their work against best practices.
- The team built a test rack modelled on a real substation: SEL-751 feeder protection relays, an SEL RTAC and Ethernet switches, driven by an OMICRON CMC test set running RelaySimTest.
- Students connect their Ignition projects to the rack, visualize simulated measurements on a single-line diagram and operate the circuit breaker over DNP3, arm-then-execute.
03 · Stack What it runs on
HMI Ignition 8.3 Perspective Relays SEL-751 feeder protection relays Field controller SEL RTAC Test set OMICRON CMC · RelaySimTest Network Ethernet switches Protocols DNP3 Breaker control Arm-then-execute - HMI
- ALM
- FLD
- PRO
04 · Outcome Commissioning
COMMISSIONINGIn progress.SCADA for Power Systems now runs as a 13-week Applied Research project in which Electrical and Mechatronics students build an Ignition 8.3 Perspective HMI for a simulated substation.
- Format
- 13-week Applied Research project
- Students
- Electrical and Mechatronics
- Platform
- Ignition 8.3 Perspective
- Test rack
- SEL-751 · SEL RTAC · OMICRON CMC
- Breaker control
- DNP3, arm-then-execute
- My part
- Reference project, assignments, study plan
- Status
- COMMISSIONING
Try the course HMI
A simulation of the course HMI's main page: click CB-1, ARM it, then OPEN or CLOSE, or simulate a fault to trip the SEL-751. Readings are replayed from FIG 4, 6 and 7.
SEL-751NORMAL
- Feeder
- ENERGISED
- CB-1
- CLOSED
- SEL-751
- NORMAL
Source
- PF98.7%
- Freq60.0Hz
Current
- IA1.9A
- IB1.8A
- IC1.8A
Voltage
- VAB100.56V
- VBC100.50V
- VCA100.58V
Power
- P326.52W
- Q52.17VAR
- S330.66VA
On the course rack, an OMICRON CMC test set running RelaySimTest drives the measurements.
Event log
0 eventssimulated · newest first
Course HMI screens
FIG 4 Main page of the course HMI (Ignition 8.3 Perspective). FIG 5 Circuit breaker popup: ARM first, then OPEN or CLOSE. FIG 6 Relay trip: the SEL-751 relay is flagged TRIPPED, and the event log records the trip and two threshold alarms. FIG 7 After the trip: the breaker and the line past it turn red, and the phase currents read 0.0 A. FIG 8 Alarm status table: six active, unacknowledged threshold alarms and eight cleared ones still to acknowledge. FIG 9 Trend chart: phase currents and voltages over the last 15 minutes.